Downlink Commands for Auxiliary Features
This section describes the JSON format for downlink commands for auxiliary features.
Configure General Parameters
| Name | Example |
|---|---|
| reboot | Reboot the
device.{
"reboot": "yes"
} |
| temperature_unit | Temperature Unit is
°F.{
"temperature_unit": 1 //00=°C, 01=°F
} |
| query_device_status | Enquiry periodic
report.{
"query_device_status": "yes"
} |
Configure Button Parameters
| Name | Example |
|---|---|
| button_custom_function | Enable Button Customization and configure the
feature for every
button.{
"button_custom_function": {
"enable": 1, //0=Disable, 1=Enable
"mode1": 1, //1=Temperature Control Mode (default), 2=Fan Mode, 6=Event 1 Report, 7=°C or °F switch
"mode2": 6, //1=Temperature Control Mode, 2=Fan Mode (default), 6=Event 1 Report, 7=°C or °F switch
"mode3": 7 //0=System On/Off (default), 6=Event 3 Report, 7=°C or °F switch
}
} |
| children_lock_settings | Enable Child
Lock.{
"children_lock_settings: 2 //1=Disable all, 2=Enable all
} |
| unlock_button | Enable temporary unlock and the unlock time is
3600s.{
"unlock_button": {
"enable": 1, //0=Disable, 1=Enable
"timeout": 3600 //Unit: s, range: 1-3600, default: 30
}
} |
| bacnet_unlock_enable | Enable Temporary
Unlock.{
"bacnet_unlock_enable": 1 //0=Disable (default), 1=Enable
} |
| bacnet_unlock_timeout | Unlock time is
3600s.{
"bacnet_unlock_timeout": 300 //Unit: s, range: 1-3600, default: 30
} |
| unlock_combination_button_settings | Configure the button combination for temporary
unlock.{
"unlock_combination_button_settings": 1 //1=button1/2, 2=button2/3, 3=button3/4, 4=button4/5, 5=button1/2/3, 6=button2/3/4, 7=all
} |
Configure Screen Parameters
| Name | Example |
|---|---|
| screen_display_settings |
Disable ambient temperature display and enable the others. {
"screen_display_settings": { //0: disable, 1: enable
"ambient_temp": 0,
"ambient_humi": 1,
"target_temp": 1,
"plan_name": 1,
"reserved": 0
}
}
|
| screen_temp_mode_enable |
Disable Temperature Control Mode Display. {
"screen_temp_mode_enable": 0 //0=Disable, 1=Enable (default)
}
|
| screen_fan_mode_enable |
Disable Fan Mode Display. {
"screen_fan_mode_enable": 0 //0=Disable, 1=Enable (default)
}
|
| screen_off_enable |
Disable display data when system off. {
"screen_off_enable": 0 //0=Not Display (display OFF), 1=Display (Default)
}
|
| intelligent_display_enable |
Disable Screen Smart Mode. {
"intelligent_display_enable": 0 //0=Disable, 1=Enable (default)
}
|
| backlight_enable |
Disable frontlight (WT401-Flat-FL Only). {
"backlight_enable": 0 //0=Disable, 1=Enable (default)
}
|
Configure Time Parameters
| Name | Example |
|---|---|
| time_zone | Set UTC Time Zone as
UTC-4.{
"time_zone: -240 //Time zone*60
} |
| daylight_saving_time | Enable DST, start time is October 1st Sunday 2:00,
end time is April 1st Sunday 2:00, bias is 60
minutes.{
"daylight_saving_time": {
"enable": 1, //0: Disable (default), 1: Enable
"daylight_saving_time_offset": 60, //Unit: min, range: 1-120
"start_month": 10, //Range: 1-12
"start_week_num": 1, //Range: 1-5
"start_week_day": 7, //Range: 1-7
"start_hour_min": 120, //Unit: min, range: 0-1439
"end_month": 4, //Range: 1-12
"end_week_num": 1, //Range: 1-5
"end_week_day": 7, //Range: 1-7
"end_hour_min": 120 //Unit: min, range: 0-1439
}
} |
| synchronize_time | Sync time from
LNS.{
"synchronize_time": "yes"
} |
Configure Calibration Parameters
| Name | Example |
|---|---|
| temperature_calibration_settings | Enable Temperature Calibration and configure the
calibration value as
-2°C.{
"temperature_calibration_settings": {
"enable": 0, //0: Disable (default), 1: Enable
"calibration_value": -2 //Unit: °C, Range: -80-80
}
} |
| humidity_calibration_settings | Enable Humidity Calibration and configure the
calibration value as
-2%RH.{
"humidity_calibration_settings": {
"enable": 0, //0: Disable (default), 1: Enable
"calibration_value": -2 //Unit: %RH, Range: -100-100
}
} |