Note: Applicable to certain brand only. Please consult Milesight sales
support before use.
Query Operating Parameters
| Command |
Direction |
Description |
| iuparam_read |
Server → Controller |
Query indoor unit operating
parameters. |
Request Example
{
"sn": 36,
"cmd": "iuparam_read",
"uuid": "fa0000014000012402201180001015134",
"body": {
"addrs": [
"1-1-1-1",
"1-2-1-2"
]
}
}Response
Example{
"sn": 36,
"cmd": "iuparam_read",
"uuid": "fa0000014000012402201180001015134",
"body": {
"iumsg": [
{
"a": "1-1-1-1",
"acs": "ff",
"cp": 40,
"ev": 100,
"tg": 18,
"tl": 50,
"tb": 28,
"to": 28,
"ts": 28,
"of": 1,
"md": 2,
"fs": 0,
"ad": 56,
"th": 1,
"mi": 0,
"mc": 0
},
{
"a": "1-2-1-2",
"acs": "6608",
"cp": 40,
"ev": 100,
"tg": 18,
"tl": 50,
"tb": 28,
"to": 28,
"ts": 28,
"of": 1,
"md": 2,
"fs": 0,
"ad": 12,
"th": 1,
"mi": 1,
"mc": 0
}
]
}
}Parameters
| Name |
Description |
| addrs |
Target indoor unit address. An empty
array applies to all indoor units. |
Response Fields
| Name |
Description |
| a |
Indoor unit address. |
| acs |
Alarm code. |
| cp |
Capacity code. |
| ev |
Electronic expansion valve
opening. |
| tg |
Gas pipe temperature. |
| tl |
Liquid pipe temperature. |
| tb |
Return air temperature. |
| to |
Supply air temperature. |
| ts |
Set temperature. |
| of |
Power status. |
| md |
Operating mode. |
| fs |
Fan speed. |
| ad |
Centralized control address. |
| th |
Thermostat status: 1 = On, 0 =
Off. |
| mi |
Master indoor unit / cooling-heating
priority status. |
| mc |