Default Parameter Values

Interface Parameter Default Description
general_write concentrator_id 1 Required. Smart controller index, corresponding to the first segment of the four-part AC address.
general_write watch 0 Optional. Enables monitoring of air conditioners running continuously for an extended period. 0 = Disabled, 1 = Enabled.
general_write watcht 300 Optional. If the continuous operating time exceeds this value (minutes), the smart controller sends a shutdown command to the corresponding air conditioner.
device_report_config act 0 Required. Enables periodic automatic reporting of AC status. 0 = Disabled, 1 = Enabled.
device_report_config interval 300 Optional. Interval for periodic AC status reporting, in seconds.
device_update_config auto 1 Required. Enables automatic reporting when AC status changes. 0 = Disabled, 1 = Enabled.
lock_write onOffLock 0 Optional. Locks the power on/off status.
lock_write modeLock 0 Optional. Locks the operating mode.
lock_write tempLock 0 Optional. Locks the set temperature.
lock_write fanSpeedLock 0 Optional. Locks the fan speed.
lock_write fanDirectLock 0 Optional. Locks the airflow direction.
lock_report_config act 0 Required. Enables periodic automatic reporting of AC lock status. 0 = Disabled, 1 = Enabled.
lock_report_config interval 300 Optional. Interval for periodic AC lock status reporting, in seconds.
lock_report_config auto 1 Required. Enables automatic reporting when AC lock status changes. 0 = Disabled, 1 = Enabled.
peak_shaving_write state 0 Optional, depending on the number of configured channels. Enables peak shaving for Channel 1. 0 = Disabled, 1 = Enabled.
peak_shaving_write state2 0 Optional, depending on the number of configured channels. Enables peak shaving for Channel 2. 0 = Disabled, 1 = Enabled.
peak_shaving_write state3 0 Optional, depending on the number of configured channels. Enables peak shaving for Channel 3. 0 = Disabled, 1 = Enabled.
peak_shaving_write state4 0 Optional, depending on the number of configured channels. Enables peak shaving for Channel 4. 0 = Disabled, 1 = Enabled.
electric_relay_write state 0 Optional, depending on the number of configured channels. Controls the relay for Channel 1. 0 = Off, 1 = On.
electric_relay_write state2 0 Optional, depending on the number of configured channels. Controls the relay for Channel 2. 0 = Off, 1 = On.
electric_relay_write state3 0 Optional, depending on the number of configured channels. Controls the relay for Channel 3. 0 = Off, 1 = On.
electric_relay_write state4 0 Optional, depending on the number of configured channels. Controls the relay for Channel 4. 0 = Off, 1 = On.