| general_write |
concentrator_id |
1 |
Required. Smart controller index,
corresponding to the first segment of the four-part AC
address. |
| general_write |
watch |
0 |
Optional. Enables monitoring of air
conditioners running continuously for an extended period.
0 = Disabled, 1 =
Enabled. |
| general_write |
watcht |
300 |
Optional. If the continuous
operating time exceeds this value (minutes), the smart controller
sends a shutdown command to the corresponding air
conditioner. |
| device_report_config |
act |
0 |
Required. Enables periodic automatic
reporting of AC status. 0 = Disabled,
1 = Enabled. |
| device_report_config |
interval |
300 |
Optional. Interval for periodic AC
status reporting, in seconds. |
| device_update_config |
auto |
1 |
Required. Enables automatic
reporting when AC status changes. 0 = Disabled,
1 = Enabled. |
| lock_write |
onOffLock |
0 |
Optional. Locks the power on/off
status. |
| lock_write |
modeLock |
0 |
Optional. Locks the operating
mode. |
| lock_write |
tempLock |
0 |
Optional. Locks the set
temperature. |
| lock_write |
fanSpeedLock |
0 |
Optional. Locks the fan
speed. |
| lock_write |
fanDirectLock |
0 |
Optional. Locks the airflow
direction. |
| lock_report_config |
act |
0 |
Required. Enables periodic automatic
reporting of AC lock status. 0 = Disabled,
1 = Enabled. |
| lock_report_config |
interval |
300 |
Optional. Interval for periodic AC
lock status reporting, in seconds. |
| lock_report_config |
auto |
1 |
Required. Enables automatic
reporting when AC lock status changes. 0 =
Disabled, 1 = Enabled. |
| peak_shaving_write |
state |
0 |
Optional, depending on the number of
configured channels. Enables peak shaving for Channel 1.
0 = Disabled, 1 =
Enabled. |
| peak_shaving_write |
state2 |
0 |
Optional, depending on the number of
configured channels. Enables peak shaving for Channel 2.
0 = Disabled, 1 =
Enabled. |
| peak_shaving_write |
state3 |
0 |
Optional, depending on the number of
configured channels. Enables peak shaving for Channel 3.
0 = Disabled, 1 =
Enabled. |
| peak_shaving_write |
state4 |
0 |
Optional, depending on the number of
configured channels. Enables peak shaving for Channel 4.
0 = Disabled, 1 =
Enabled. |
| electric_relay_write |
state |
0 |
Optional, depending on the number of
configured channels. Controls the relay for Channel 1.
0 = Off, 1 = On. |
| electric_relay_write |
state2 |
0 |
Optional, depending on the number of
configured channels. Controls the relay for Channel 2.
0 = Off, 1 = On. |
| electric_relay_write |
state3 |
0 |
Optional, depending on the number of
configured channels. Controls the relay for Channel 3.
0 = Off, 1 = On. |
| electric_relay_write |
state4 |
0 |
Optional, depending on the number of
configured channels. Controls the relay for Channel 4.
0 = Off, 1 = On. |