Monitoring Objects

The objects in this section are used by the BMS to monitor device status, environmental measurements and operating parameters.

Device Information

Object ID Object Type Range Value Unit Remark
product_sn CSV 16 characters - (95) -
tsl_version CSV 4 characters - (95) -
version.firmware_version CSV 12 characters - (95) -
version.hardware_version CSV 4 characters - (95) -
oem_id CSV 4 characters - (95) -

Environmental and Operating Status

Object ID Object Type Range Value Unit Remark
battery AI 0-100 % (98) -
celsius_temperature AI -20-60 °C (62) -
fahrenheit_temperature AI -4-140 °F (64) -
humidity AI 0-100 %RH (29) -
pir_status MSI 0=Vacant, 1=Occupied, 2=Night Occupied - (95) -
temperature_mode MSI 0=heat, 1=em heat, 2=cool, 3=auto, 4=dehumidify, 5=ventilation - (95) -
fan_mode MSI 0=auto, 1=circulate, 2=on, 3=low, 4=medium, 5=high - (95) -
execution_plan_id MSI 0=plan0, 1=plan1, ..., 7=plan7, 255=Not executed - (95) -
celsius_target_temperature1 AI 5-35 °C (62) -
fahrenheit_target_temperature1 AI 41-95 °F (64) -
celsius_target_temperature2 AI 5-35 °C (62) Cool Target Temperature (Dual Mode)
fahrenheit_target_temperature2 AI 41-95 °F (64)