Writable Configuration Objects

The objects in this section allow the BMS to change supported WT401 settings or trigger an action.

Data Source

Object ID Object Type Default Value Range Value Unit Remark
collection_interval.seconds_of_time AV 60 1-3600 s (73) -
data_sync_to_peer MSV 0 0=Embedded, 1=Lora - (95) -
data_sync_timeout AV 10 1-60 min (72) -
celsius_origin_temperature AV 0 -20-60 °C (62) -
fahrenheit_origin_temperature AV 32 -4-140 °F (64) -
origin_humidity AV 0 0-100 %RH (29) -

Temperature and Fan Control

Object ID Object Type Default Value Range Value Unit Remark
system_status BV 0 0=off, 1=on - (95) -
mode_enable MSV 6 1=heat/em heat/cool/auto, 2=heat/cool/auto, 3=heat, 4=cool, 5=heat/cool, 6=heat/em heat/cool/auto/dehumidify/ventilation - (95) -
temperature_control_mode.mode MSV 0 0=heat, 1=em heat, 2=cool, 3=auto, 4=dehumidify, 5=ventilation - (95) -
target_temperature_mode MSV 0 0=single target, 1=dual target - (95) -
target_temperature_resolution MSV 0 0=0.5, 1=1 - (95) -
target_temperature_settings.celsius_auto AV 23 5-35 °C (62) -
target_temperature_settings.celsius_cool AV 28 5-35 °C (62) -
target_temperature_settings.celsius_heat AV 17 5-35 °C (62) -
target_temperature_settings.fahrenheit_auto AV 73.4 41-95 °F (64) -
target_temperature_settings.fahrenheit_cool AV 82.4 41-95 °F (64) -
target_temperature_settings.fahrenheit_heat AV 62.6 41-95 °F (64) -
celsius_minimum_dead_zone AV 5 1-10 K (121) -
fahrenheit_minimum_dead_zone AV 9 1.8-18 ΔT°F (120) -
target_temperature_range.auto.celsius_max AV 35 5-35 °C (62) -
target_temperature_range.auto.celsius_min AV 10 5-35 °C (62) -
target_temperature_range.auto.fahrenheit_max AV 95 41-95 °F (64) -
target_temperature_range.auto.fahrenheit_min AV 50 41-95 °F (64) -
target_temperature_range.cool.celsius_max AV 35 5-35 °C (62) -
target_temperature_range.cool.celsius_min AV 23 5-35 °C (62) -
target_temperature_range.cool.fahrenheit_max AV 95 41-95 °F (64) -
target_temperature_range.cool.fahrenheit_min AV 73.4 41-95 °F (64) -
target_temperature_range.heat.celsius_max AV 19 5-35 °C (62) -
target_temperature_range.heat.celsius_min AV 10 5-35 °C (62) -
target_temperature_range.heat.fahrenheit_max AV 66.2 41-95 °F (64) -
target_temperature_range.heat.fahrenheit_min AV 50 41-95 °F (64) -
fan_enable MSV 1 1=auto/circulate/low/medium/high, 2=auto/low/medium/high, 3=circulate/low/medium/high, 4=auto/circulate, 5=low/medium/high - (95) -
fan_control_mode MSV 0 0=auto, 1=circulate, 2=on, 3=low, 4=medium, 5=high - (95) -

Occupancy Detection

Object ID Object Type Default Value Range Value Unit Remark
pir_common.enable BV 1 0=disable, 1=enable - (95) Occupancy Detection
pir_common.release_time AV 30 1-360 min (72) -
pir_energy.enable BV 1 0=disable, 1=enable - (95) Energy-saving setting
pir_energy.plan.occupied MSV 0 0=plan0, 1=plan1, ..., 7=plan7, 255=Not executed - (95) -
pir_energy.plan.unoccupied MSV 1 - (95) -
pir_night.enable BV 0 0=disable, 1=enable - (95) Night setting
pir_night.night_time.start AV 1260 0-1439 min (72) -
pir_night.night_time.stop AV 480 0-1439 min (72) -
pir_night.occupied MSV 2 0=plan0, 1=plan1,..., 7=plan7, 255=Not executed - (95) -

Network & Communication

Object ID Object Type Default Value Range Value Unit Remark
communication_mode MSV 2 0=BLE, 1=LoRa, 2=BLE+LoRa - (95) -
communicate_interval.ble_lora.minutes_of_time AV 2 1-30 min (72) BLE Transfer Interval
communicate_interval.ble.minutes_of_time AV 2 1-30 min (72)
reporting_interval.ble_lora.minutes_of_time AV 1440 1-1440 min (72) -
reporting_interval.lora.minutes_of_time AV 10 1-1440 min (72) -
lorawan_configuration_settings.mode MSV 0 0=ClassA, 2=ClassC - (95) -

General Parameters

Object ID Object Type Default Value Range Value Unit Remark
temperature_unit MSV 0 0=Celsius, 1=Fahrenheit - (95) -
intelligent_display_enable BV 1 0=disable, 1=enable - (95) -
backlight_enable BV 1 0=disable, 1=enable - (95) WT401-Flat-FL Only
children_lock_settings MSV 1 1=disable all, 2=enable all - (95) -
bacnet_unlock_enable BV 0 0=disable, 1=enable - (95) -
bacnet_unlock_timeout AV 30 1-3600 s (73) -
unlock_combination_button_settings MSV 1 1=button1/button2, 2=button2/button3, 3=button3/button4, 4=button4/button5, 5=button1/button2/button3, 6=button2/button3/button4, 7=button1/button2/button 3/button 4/button 5 - (95) -
button_custom_function.enable BV 0 0=disable, 1=enable - (95) -
button_custom_function.mode1 MSV 1 1=Temperature Control Mode, 2=Fan Mode, 6=Button Event1, 7=Temperature Unit Switch - (95) -
button_custom_function.mode2 MSV 2 1=Temperature Control Mode, 2=Fan Mode, 6=Button Event2, 7=Temperature Unit Switch - (95) -
button_custom_function.mode3 MSV 0 0=System On/Off, 6=Button Event3, 7=Temperature Unit Switch - (95) -
synchronize_time BO - 1=yes - (95) -
time_zone MSV 0 see Time Zone Values - (95) -

Time Zone Values

Value (min) UTC Offset
-720 UTC-12
-660 UTC-11
-600 UTC-10
-570 UTC-9:30
-540 UTC-9
-480 UTC-8
-420 UTC-7
-360 UTC-6
-300 UTC-5
-240 UTC-4
-210 UTC-3:30
-180 UTC-3
-120 UTC-2
-60 UTC-1
0 UTC
60 UTC+1
120 UTC+2
180 UTC+3
210 UTC+3:30
240 UTC+4
270 UTC+4:30
300 UTC+5
330 UTC+5:30
345 UTC+5:45
360 UTC+6
390 UTC+6:30
420 UTC+7
480 UTC+8
540 UTC+9
570 UTC+9:30
600 UTC+10
630 UTC+10:30
660 UTC+11
720 UTC+12
765 UTC+12:45
780 UTC+13
840 UTC+14