Alarm Report
The device reports the following types of alarm packets.
Packet description:
| Item | Channel | Type | Description |
|---|---|---|---|
| Temperature Alarm | 83 | 67 |
Byte 1-2: Ambient Temperature, INT16/100, Unit: °C
|
| Valve Descaling Alarm | 84 | 92 | Byte 1: Current Valve Opening,
UINT8, Unit: % Byte 2: Mode, 00 = Automatic, 01 = Manual Byte 3: Result, 00 = Success, 01 = FailureByte 4: Reason
|
| Open Window Alarm | 85 | 67 | Byte 1-2: Ambient Temperature,
INT16/100, Unit: °C Byte 3: 00=Window close, 01=Window open |
| Freeze Protection Alarm | 86 | 67 | Byte 1-2: Ambient Temperature,
INT16/100, Unit: °C Byte 3: 00=Protection close, 01=Protection open Byte 4: Current Valve Opening, UINT8, Unit: % |
| Temperature Source Alarm | 87 | 00 | 00=Alarm release, 01=Alarm |
| Low Battery Alarm | 88 | 00 | 00=Alarm release, 01=Alarm |
- Examples:
-
- Low battery alarm: Report once every 26 seconds when it enters low
battery mode, for a total of three reports.
880001 Channel Type Value 88 00 01=Low battery alarm - Temperature alarm: Report once when the ambient temperature reaches the
threshold.
8367 9e0a01 Channel Type Value 83 67 Ambient temperature: 9e 0a => 0a 9e=2718/100=27.18°C
01=Above threshold
- Temperature source alarm: Report when no valid external temperature
command is received within the timeout period and the internal NTC
sensor is faulty.
870001 Channel Type Value 87 00 01=Temperature source alarm
- Low battery alarm: Report once every 26 seconds when it enters low
battery mode, for a total of three reports.