Periodic Data Packet

The device reports a data packet at a configured reporting interval.

Packet description:
Item Channel Type Byte Description
Scale Level Control Report 14 d0 8 Byte 1: Battery Level, UINT8, Unit: %

Byte 2: Current Valve Opening, UINT8, Unit: %

Byte 3-4: Ambient Temperature, INT16/100, Unit: °C

Byte 5-6: Target Temperature, INT16/100, Unit: °C

Byte 7: Current Scale Level, UINT8

Byte 8: Reporting Reason
  • 00 = Periodic Report
  • 01 = Local Modification
  • 02 = Query Response
  • 03 = Enter Non-heating Period
  • 04 = Temperature Control Enabled During Non-heating Period
  • 05 = Valve in Emergency Position
Integrated Control Report 15 d1 7 Byte 1: Battery Level, UINT8, Unit: %

Byte 2: Current Valve Opening, UINT8, Unit: %

Byte 3-4: Ambient Temperature, INT16/100, Unit: °C

Byte 5-6: Target Temperature, INT16/100, Unit: °C

Byte 7: Reporting Reason
  • 00 = Periodic Report
  • 01 = Local Modification
  • 02 = Query Response
  • 03 = Enter Non-heating Period
  • 04 = Temperature Control Enabled During Non-heating Period
  • 05 = Valve in Emergency Position
Valve Opening Control Report 16 d2 6 Byte 1: Battery Level, UINT8, Unit: %

Byte 2: Current Valve Opening, UINT8, Unit: %

Byte 3-4: Ambient Temperature, INT16/100, Unit: °C

Byte 5: Target Valve Opening, UINT8, Unit: %

Byte 6: Reporting Reason
  • 00 = Periodic Report
  • 01 = Local Modification
  • 02 = Query Device Status
  • 03 = Enter Non-heating Period
  • 04 = Temperature Control Enabled During Non-heating Period
  • 05 = Valve in Emergency Position
Temperature Control Disabled Report 17 d3 3 Byte 1: Battery Level, UINT8, Unit: %

Byte 2: Current Valve Opening, UINT8, Unit: %

Byte 3: Reporting Reason
  • 00 = Periodic Report
  • 01 = Local Modification
  • 02 = Query Response
  • 03 = Enter Non-heating Period
  • 04 = Temperature Control Enabled During Non-heating Period
  • 05 = Valve in Emergency Position
Example:
  1. Periodic report when temperature control is disabled.
    17d3 646400
    Channel Type Value
    17 d3 Battery Level: 64=>100%

    Current Valve Opening: 64=>100%

    Reporting Reason: 00 = Periodic Report

  2. Periodic packet for Scale Level Control Mode.
    14d0 6400 6309 6c07 0400
    Channel Type Value
    14 d0

    Battery Level: 64=>100%

    Current Valve Opening: 00=> 0%

    Ambient Temperature: 63 09 =>09 63=2403/100=24.03 °C

    Target Temperature: 6c 07 => 07 6c = 1900/100=19 °C

    Current Scale Level: 04=Level 4

    Reporting Reason: 00 = Periodic Report

  3. Periodic packet for Integrated Control mode.
    15d1 6400 6309 6c0700
    Channel Type Value
    15 d1

    Battery Level: 64=>100%

    Current Valve Opening: 00=> 0%

    Ambient Temperature: 63 09 =>09 63=2403/100=24.03 °C

    Target Temperature: 6c 07 => 07 6c = 1900/100=19 °C

    Reporting Reason: 00 = Periodic Report

  4. Periodic packet for Valve Opening Control mode.
    16d2 6400 6309 3200
    Channel Type Value
    16 d2

    Battery Level: 64=>100%

    Current Valve Opening: 00=> 0%

    Ambient Temperature: 63 09 =>09 63=2403/100=24.03 °C

    Target Valve Opening: 32=>50%

    Reporting Reason: 00 = Periodic Report