Periodic Data Packet
The device reports a data packet at a configured reporting interval.
| Item | Channel | Type | Byte | Description |
|---|---|---|---|---|
| Scale Level Control Report | 14 | d0 | 8 | Byte 1: Battery Level, UINT8,
Unit: % Byte 2: Current Valve Opening, UINT8, Unit: % Byte 3-4: Ambient Temperature, INT16/100, Unit: °CByte 5-6: Target Temperature, INT16/100, Unit: °C Byte 7: Current Scale Level, UINT8 Byte
8: Reporting Reason
|
| Integrated Control Report | 15 | d1 | 7 | Byte 1: Battery Level, UINT8,
Unit: % Byte 2: Current Valve Opening, UINT8, Unit: % Byte 3-4: Ambient Temperature, INT16/100, Unit: °CByte 5-6: Target Temperature, INT16/100, Unit: °C Byte 7: Reporting Reason
|
| Valve Opening Control Report | 16 | d2 | 6 | Byte 1: Battery Level, UINT8,
Unit: % Byte 2: Current Valve Opening, UINT8, Unit: % Byte 3-4: Ambient Temperature, INT16/100, Unit: °CByte 5: Target Valve Opening, UINT8, Unit: % Byte 6: Reporting Reason
|
| Temperature Control Disabled Report | 17 | d3 | 3 | Byte 1: Battery Level, UINT8,
Unit: % Byte 2: Current Valve Opening, UINT8, Unit: % Byte 3: Reporting Reason
|
- Example:
-
- Periodic report when temperature control is disabled.
17d3 646400 Channel Type Value 17 d3 Battery Level: 64=>100% Current Valve Opening: 64=>100%
Reporting Reason: 00 = Periodic Report
- Periodic packet for Scale Level Control Mode.
14d0 6400 6309 6c07 0400 Channel Type Value 14 d0 Battery Level: 64=>100%
Current Valve Opening: 00=> 0%
Ambient Temperature: 63 09 =>09 63=2403/100=24.03 °C
Target Temperature: 6c 07 => 07 6c = 1900/100=19 °C
Current Scale Level: 04=Level 4
Reporting Reason: 00 = Periodic Report
- Periodic packet for Integrated Control mode.
15d1 6400 6309 6c0700 Channel Type Value 15 d1 Battery Level: 64=>100%
Current Valve Opening: 00=> 0%
Ambient Temperature: 63 09 =>09 63=2403/100=24.03 °C
Target Temperature: 6c 07 => 07 6c = 1900/100=19 °C
Reporting Reason: 00 = Periodic Report
- Periodic packet for Valve Opening Control mode.
16d2 6400 6309 3200 Channel Type Value 16 d2 Battery Level: 64=>100%
Current Valve Opening: 00=> 0%
Ambient Temperature: 63 09 =>09 63=2403/100=24.03 °CTarget Valve Opening: 32=>50%
Reporting Reason: 00 = Periodic Report
- Periodic report when temperature control is disabled.