Configure the Locks Status
| Command |
Direction |
Description |
| lock_write |
Server → Controller |
Enable air conditioning
parameter lock. |
Request Example
{
"sn": 14,
"cmd": "lock_write",
"uuid": "fa0000014000012402201180001015134",
"body": {
"addrs": [
"16-1-1-1",
"16-1-2-1"
],
"onOffLock": 1,
"onOff": 1,
"modeLock": 1,
"workMode": 1,
"tempLock": 1,
"tempSetLo": 24,
"tempSetHi": 26,
"fanSpeedLock": 1,
"fanSpeed": 0,
"fanDirectLock": 1,
"fanDirect": 0
}
}
Response Example
{
"sn": 14,
"cmd": "lock_write",
"uuid": "fa0000014000012402201180001015134",
"body": {
"errorCode": 0
}
}
Parameters
| Name |
Description |
| addrs |
Target air conditioner
address. |
| onOffLock |
Power lock: 0 = Not locked; 1 =
Lock |
| onOff |
Power status to be locked. |
| modeLock |
Mode lock: 0 = Not locked; 1 = Lock
|
| workMode |
Working mode(s) to be locked
- 1 = Cool
- 2 = Heat
- 3 = Ventilation
- 4 = Dehumidification
- 10 = Heat/Ventilation
- 11 = Cool/Ventilation
- 12 = Cool/Dehumidification
- 13 = Cool/Dehumidification/Ventilation
- 14 = Dehumidification/Ventilation
|
| tempLock |
Temperature lock: 0 = Not locked; 1
= Lock |
| tempSetLo |
Minimum set temperature, range:
16–31°C. |
| tempSetHi |
Maximum set temperature, range:
16–31°C. |
| fanSpeedLock |
Fan speed lock. Reserved. |
| fanSpeed |
Fan speed value. |
| fanDirectLock |
Airflow direction lock.
Reserved. |
| fanDirect |
Airflow direction value. |
Response Filed
| Name |
Description |
| errorCode |
0: Command received successfully.
For other values, see ErrorCode. |
Query the Lock Status
| Command |
Direction |
Description |
| lock_status_read |
Server → Controller |
Query the air conditioning lock
status.
- all: All air conditioning
- addrs: Specified air conditioning
|
Request Example
{
"sn": 15,
"cmd": "lock_status_read",
"uuid": "fa0000014000012402201180001015134",
"body": {
"cmd": "all"
}
}
Response Example
{
"sn": 15,
"cmd": "lock_status_read",
"uuid": "fa0000014000012402201180001015134",
"body": {
"cmd": "all",
"inUnitMessages": [
{
"a": "1-1-1-1",
"ol": 0,
"onOff": 1,
"ml": 0,
"workMode": 1,
"tl": 0,
"tsl": 24,
"tsh": 26,
"t": 1
},
],
}
}
Parameters
| Name |
Description |
| cmd |
all or addrs. |
| addrs |
Specified air conditioning
addrs. |
Response Filed
| Name |
Description |
| a |
Air conditioner address. |
| ol |
Power lock status. |
| onOff |
Locked power status. |
| ml |
Mode lock status. |
| workMode |
Locked working mode. |
| tl |
Temperature lock status. |
| tsl |
Minimum set temperature. |
| tsh |
Maximum set temperature. |
| t |
Scheduled status: 0 = No, 1 =
Yes. |
Configure Automatic Reporting of Lock Status
| Command |
Direction |
Description |
| lock_report_config |
Server → Controller |
Enable or disable periodic
reporting of air conditioner lock status and configures the
reporting interval. |
Request Example
{
"sn": 16,
"cmd": "lock_report_config",
"uuid": "fa0000014000012402201180001015134",
"body": {
"act": 0,
"interval": 300
}
}
Response Example
{
"sn": 16,
"cmd": "lock_report_config",
"uuid": "fa0000014000012402201180001015134",
"body": {
"errorCode": 0
}
}
{
"sn": 0,
"cmd": "lock_status_report",
"uuid": "fa0000014000012402201180001015134",
"body": {
"cmd":"addrs",
"inUnitMessages": [
{
"a": "1-1-1-1",
"ol": 0,
"ml": 0,
"tl": 0,
"tsl": 24,
"tsh": 26,
"fsl": 0,
"fdl": 0,
}
]
}
}
Parameters
| Name |
Description |
| act |
0 = Disabled (default), 1 =
Enabled. |
| interval |
Reporting interval, Unit: s.
Default: 300s. |
Response Filed
| Name |
Description |
| errorCode |
0: Command received successfully.
For other values, see ErrorCode. |
Query Periodic Lock Status Reporting Configuration
| Command |
Direction |
Description |
| lock_report_config_read |
Server → Controller |
Query whether periodic lock
status reporting is enabled and the reporting interval. |
Request Example
{
"sn": 17,
"cmd": "lock_report_config_read",
"uuid": "fa0000014000012402201180001015134",
"body": {
}
}
Response Example
{
"sn": 17,
"cmd": "lock_report_config_read",
"uuid": "fa0000014000012402201180001015134",
"body": {
"act": 0,
"interval": 300
"errorCode":0
}
}
Response Filed
| Name |
Description |
| act |
0 = Disabled, 1 = Enabled. |
| interval |
Reporting interval, Unit: s. |
| errorCode |
0: Command received successfully.
For other values, see ErrorCode. |
Configure Automatic Reporting of Lock Status
Changes
| Command |
Direction |
Description |
| lock_update_config |
Server → Controller |
Enable or disable automatic
reporting of lock status changes. |
| lock_status_report |
Controller → Server |
Report air conditioner lock
status changes. |
Request Example
{
"sn": 18,
"cmd": "lock_update_config",
"uuid": "fa0000014000012402201180001015134",
"body": {
"auto": 1,
}
}
Response Example
{
"sn": 18,
"cmd": "lock_update_config",
"uuid": "fa0000014000012402201180001015134",
"body": {
"errorCode": 0
}
}
{
"sn": 0,
"cmd": "lock_status_report",
"uuid": "fa0000014000012402201180001015134",
"body": {
"cmd":"addrs",
"inUnitMessages": [
{
"a": "1-1-1-1",
"ol": 0,
"ml": 0,
"tl": 0,
"tsl": 24,
"tsh": 26,
"fsl": 0,
"fdl": 0,
}
]
}
}
Parameters
| Name |
Description |
| auto |
0 = Disabled, 1 = Enabled
(default). |
Response Filed
| Name |
Description |
| errorCode |
0: Command received successfully.
For other values, see ErrorCode. |
Query Automatic Reporting of Lock Status Changes
| Command |
Direction |
Description |
| lock_update_config_read |
Server → Controller |
Query whether automatic
reporting of lock status changes is enabled. |
Request Example
{
"sn": 19,
"cmd": "lock_update_config_read",
"uuid": "fa0000014000012402201180001015134",
"body": {
}
}
Response Example
{
"sn": 19,
"cmd": "lock_update_config_read",
"uuid": "fa0000014000012402201180001015134",
"body": {
"auto": 1,
"errorCode":0
}
}
Response Filed
| Name |
Description |
| auto |
0 = Disabled, 1 = Enabled. |
| errorCode |
0: Command received successfully.
For other values, see ErrorCode. |
Configure Batch Lock Status
| Command |
Direction |
Description |
| lock_write_batch |
Server → Controller |
Batch configure the lock status
of air conditioners. |
Request
Example
{
"sn": 42,
"cmd": "lock_write_batch",
"uuid": "fa0000014000012402201180001015134",
"body": {
“batchCmd”: [
{
"addrs": "16-1-1-1",
"onOffLock": 0,
"onOff": 1,
"modeLock": 0,
"workMode": 1,
"tempLock": 0,
"tempSetLo": 24,
"tempSetHi": 26,
"fanSpeedLock": 0,
"fanSpeed": 0,
"fanDirectLock": 0,
"fanDirect": 0
},
{
"addrs": "16-1-1-2",
"onOffLock": 0,
"onOff": 1,
"modeLock": 0,
"workMode": 1,
"tempLock": 0,
"tempSetLo": 24,
"tempSetHi": 26,
"fanSpeedLock": 0,
"fanSpeed": 0,
"fanDirectLock": 0,
"fanDirect": 0
}
]
}
}Response
Example{
"sn": 42,
"cmd": "lock_write_batch",
"uuid": "fa0000014000012402201180001015134",
"body": {
"errorCode": 0
}
}Parameters
| Name |
Description |
| batchCmd |
Multiple Lock Commands |
| addrs |
Target air conditioner
address. |
| onOffLock |
Power lock: 0 = Not locked; 1 =
Lock |
| onOff |
Power status to be
locked. |
| modeLock |
Mode lock: 0 = Not locked; 1 =
Lock |
| workMode |
Working mode(s) to be locked
- 1 = Cool
- 2 = Heat
- 3 = Ventilation
- 4 = Dehumidification
- 10 = Heat/Ventilation
- 11 = Cool/Ventilation
- 12 = Cool/Dehumidification
- 13 = Cool/Dehumidification/Ventilation
- 14 = Dehumidification/Ventilation
|
| tempLock |
Temperature lock: 0 = Not
locked; 1 = Lock |
| tempSetLo |
Minimum set temperature, range:
16–31°C. |
| tempSetHi |
Maximum set temperature, range:
16–31°C. |
| fanSpeedLock |
Fan speed lock.
Reserved. |
| fanSpeed |
Fan speed value. |
| fanDirectLock |
Airflow direction lock.
Reserved. |
| fanDirect |
Airflow direction value. |
Response Fields
| Name |
Description |
| errorCode |
0: Command received
successfully. For other values, see ErrorCode. |
Create a Schedule
| Command |
Detection |
Description |
| schedule_write |
Server → Controller |
Writes scheduled tasks. Supports
up to 64 tasks. |
Request Example
{
"sn": 20,
"cmd": "schedule_write",
"uuid": "fa0000014000012402201180001015134",
"body": {
"schNo": 1,
"addrs": [
"1-1-1-1",
"1-1-1-2"
],
"pointTime": "7:30",
"startDate": "2021-04-01",
"endDate": "2021-04-10",
"exclDate": [
"2021-04-03",
"2021-04-05"
],
"scheInfo": {
"action": 1,
"onOff": 1,
"tempSet": 24,
"workMode": 1,
"fanSpeed": 1,
"fanDirect": 1,
"onOffLock": 1,
"modeLock": 1,
"tempLock": 1,
"tempSetLo": 24,
"tempSetHi": 26,
"fanSpeedLock": 0,
"fanDirectLock": 0
}
}
}
Response Example
{
"sn": 20,
"cmd": "schedule_write",
"uuid": "fa0000014000012402201180001015134",
"body": {
"errorCode": 0
}
}
Parameters
| Name |
Description |
| schNo |
Scheduled ID. |
| addrs |
Target air conditioner
address. |
| pointTime |
Execution time. |
| startDate / endDate |
Effective date range. |
| exclDate |
List of excluded dates. |
| scheInfo.action |
- 0 = Power off
- 1 = Power on
- 2 = Power off and lock
- 3 = Unlock power control
- 4 = Unlock and power on
- 7 = Apply lock settings
|
| scheInfo.Control |
Used when action = 1. Includes
onOff, tempSet, workMode, fanSpeed, and fanDirect. |
| scheInfo.Lock |
Used when action = 7. Includes
onOffLock, modeLock, tempLock, tempSetLo/Hi, etc.
Note: When enabling the lock function,
adjust any non-compliant settings first. For example, to
lock the air conditioner in the off state, turn it off
before applying the lock.
|
Response Filed
| Name |
Description |
| errorCode |
0: Command received successfully.
For other values, see ErrorCode. |
Query the Schedule
| Command |
Detection |
Description |
| schedule_read |
Server → Controller |
Query the air conditioner
schedule information. |
Request Example
{
"sn": 23,
"cmd": "schedule_read",
"uuid": "fa0000014000012402201180001015134",
"body": {
"schNos": [1],
}
}
Response Example
{
"sn": 23,
"cmd": "schedule_read",
"uuid": "fa0000014000012402201180001015134",
"body": {
"items": [
{
"schNo": 1,
"addrs": [
"1-1-1-1",
"1-1-1-2"
],
"type": "v",
"pointTime": "7:30",
"startDate": "2021-04-01",
"endDate": "2021-04-10",
"scheInfo": {
"action": 1,
"onOff": 1,
"tempSet": 24,
"workMode": 1,
"fanSpeed": 1,
"fanDirect": 1,
"onOffLock": 1,
"modeLock": 1,
"tempLock": 1,
"tempSetLo": 24,
"tempSetHi": 26
}
},
]
}
}
Parameters
| Name |
Description |
| schNos |
Scheduled task ID. Empty array
queries all scheduled tasks. |
Response Filed
| Name |
Description |
| schNo |
Scheduled task ID |
| addrs |
Air conditioner address |
| type |
v: Refrigerant-system air
conditioner |
| pointTime |
Execution time. |
| startDate/endDate |
Effective date range. |
| scheInfo |
Scheduled action parameters. |
Delete a Schedule
| Command |
Detection |
Description |
| schedule_delete |
Server → Controller |
Delete the air conditioning
schedule. |
Request Example
{
"sn": 24,
"cmd": "schedule_delete",
"uuid": "fa0000014000012402201180001015134",
"body": {
"schNos": [1],
}
}
Response Example
{
"sn": 24,
"cmd": "schedule_delete",
"uuid": "fa0000014000012402201180001015134",
"body": {
"errorCode": 0
}
}
Parameters
| Name |
Description |
| schNos |
Scheduled task ID. Empty array
queries all scheduled tasks. |
Response Filed
| Name |
Description |
| errorCode |
0: Command received successfully.
For other values, see ErrorCode. |
Query the Runtime
| Command |
Direction |
Description |
| energy_read |
Server → Controller |
Query the accumulated working
time within the specified time range. |
Request
Example
{
"sn": 27,
"cmd": "energy_read",
"uuid": "fa0000014000012402201180001015134",
"body": {
"runtime": {
"timeRange": "202102031800~202102032000",
"addrs": [
"1-1-8-9",
"1-1-8-10"
],
"si":"s"
}
}
}Response
Example{
"sn": 27,
"cmd": "energy_read",
"uuid": "fa0000014000012402201180001015134",
"body": {
"sn": "a",
"timeRange": "202102031800~202102032000",
"runtime": [
{
"a": "1-1-8-9",
"i": [
{
"r":"20"
}
],
"C":"71"
},
{
"a": "1-1-8-10",
"i": [
{
"r":"20"
}
],
"C":"71"
}
]
}
}Parameters
| Name |
Description |
| timeRange |
Query time range. The start and end
times must be on the hour. |
| addrs |
Indoor unit address. An empty array
queries all indoor units. |
| si |
Equivalent flag bit. Include this
field in the first request packet only. Continue sending read
commands until the final packet is received. Do not include
"si":"s" in subsequent requests. |
Response Fields
| Name |
Description |
| sn |
Packet sequence flag for segmented
transmission. "a" indicates a non-final packet;
"e" indicates the final packet. |
| timeRange |
Query time range. |
| a |
Indoor unit address. |
| r |
Accumulated operating time within
the specified period, Unit; min. |
| C |
Indoor unit capacity. |
Query the Equivalent Data
| Command |
Key |
Direction |
Description |
| energy_read |
shareEquivalents |
Server → Controller |
Query equivalent value
information for air conditioners within the specified time
range. |
Request
Example
{
"sn": 28,
"cmd": "energy_read",
"uuid": "fa0000014000012402201180001015134",
"body": {
"shareEquivalents": {
"timeRange": "202102031800~202102032000",
"addrs": [
"1-1-8-9",
"1-1-8-10"
],
"si":"s"
}
}
}Response
Example{
"sn": 28,
"cmd": "energy_read",
"uuid": "fa0000014000012402201180001015134",
"body": {
"sn": "a",
"timeRange": "202102031800~202102032000",
"shareEquivalents": [
{
"a": "1-1-8-9",
"i": [
{
"t": "202102032000",
"X": "8.6"
}
],
"C":"71"
},
{
"a": "1-1-8-10",
"i": [
{
"t": "202102032000",
"X": "65.2"
}
],
"C":"71"
}
]
}
}Parameters
| Name |
Description |
| timeRange |
Query time range. The start and end
times must be on the hour. |
| addrs |
Indoor unit address. An empty array
queries all indoor units. |
| si |
Equivalent flag bit. Include this
field in the first request packet only. Continue sending read
commands until the final packet is received. Do not include
"si":"s" in subsequent requests. |
Response Fields
| Name |
Description |
| sn |
Packet sequence flag for segmented
transmission. "a" indicates a non-final packet;
"e" indicates the final packet. |
| timeRange |
Query time range. |
| a |
Indoor unit address. |
| t |
Query end time. |
| X |
Sum of equivalent values within the
specified time range. |
| C |
Indoor unit capacity. |
Query the Operation Logs
| Command |
Direction |
Description |
| energy_read |
Server → Controller |
Query the air conditioner
operation records. |
Request Example
{
"sn": 35,
"cmd": "energy_read",
"uuid": "fa0000014000012402201180001015134",
"body": {
"operateLogs": {
"timeRange": "202102031800~202102031900",
"addrs": [
"1-1-8-9",
"1-1-8-10"
]
}
}
}
Response Example
{
"sn": 35,
"cmd": "energy_read",
"uuid": "fa0000014000012402201180001015134",
"body": {
"timeRange": "202102031800~202102031900",
"operateLogs": [
{
"a": "1-1-8-9",
"i": [
{
"t": "202102031800",
"o": 1,
"ts": 24,
"w": 1,
"fs": 1,
"fd": 1,
"a": ""
},
{
"t": "202102031805",
"o": 1,
"ts": 24,
"w": 1,
"fs": 1,
"fd": 1,
"a": "LOST"
}
]
},
{
"a": "1-1-8-10",
"i": [
{
"t": "202102031800",
"o": 1,
"ts": 24,
"w": 1,
"fs": 1,
"fd": 1,
"a": "U5"
},
{
"t": "20210203180110",
"o": 1,
"ts": 24,
"w": 1,
"fs": 1,
"fd": 1,
"a": "6686"
}
]
}
]
}
}
Parameters
| Name |
Description |
| timeRange |
Query time range. The start and end
times must be on the hour. |
| addrs |
Indoor unit address. An empty array
queries all indoor units. |
Response Fields
| Name |
Description |
| timeRange |
Query time range. |
| a |
Indoor unit address. |
| t |
Timestamp. |
| o |
Power status. |
| ts |
Set temperature. |
| w |
Working mode. |
| fs |
Fan speed. |
| fd |
Airflow direction. |
| a |
Fault code. Empty indicates no
fault, LOST indicates offline or not discovered. |
Start Load Regulation
| Command |
Direction |
Description |
| start_regulate |
Server → Controller |
Enable load control
mode. |
Request
Example
{
"sn": 38,
"cmd": "start_regulate",
"uuid": "fa0000014000012402201180001015134",
"body": {
"addrs": [
"1-1-1-1",
"1-2-1-2"
],
"end":"2023-11-24 09:26:59",
"trempCtl": 0,
"modelCtl": 0,
"onOffCtl": 0
}
}Response
Example{
"sn": 38,
"cmd": "start_regulate",
"uuid": "fa0000014000012402201180001015134",
"body": {
"errorCode":0
}
}Parameters
| Name |
Description |
| addrs |
Target air conditioner address. An
empty array applies to all air conditioners. |
| end |
Load control end time. |
| trempCtl |
User temperature control: 0 =
Allowed, 1 = Not allowed. |
| modelCtl |
User mode control: 0 = Allowed, 1 =
Not allowed. |
| onOffCtl |
User power control: 0 = Allowed, 1 =
Not allowed. |
Response Fields
| Name |
Description |
| errorCode |
0: Command received successfully.
For other values, see ErrorCode. |
End Load Regulation
| Command |
Direction |
Description |
| end_regulate |
Server → Controller |
Disable load control mode. |
Request
Example
{
"sn": 39,
"cmd": "end_regulate",
"uuid": "fa0000014000012402201180001015134",
"body": {
}
}Response
Example{
"sn": 39,
"cmd": "end_regulate",
"uuid": "fa0000014000012402201180001015134",
"body": {
"errorCode":0
}
}Response Fields
| Name |
Description |
| errorCode |
0: Command received successfully.
For other values, see ErrorCode. |