Module B: Indoor Unit Parameter Block
Base: D24000
Address rule: Channel x (1-4), Unit U (1-160) -> D(24000 + (X-1) * 2560 + (U-1) * 16 + field_offset)
| Offset | Register Address | Byte/Bit | Field ID | Function Description | Function Code | R/W |
|---|---|---|---|---|---|---|
| +00 | D24000 (Ch1 U1) | Whole Register | D24000 | Indoor Unit U - Outdoor Unit Address (0-254, >254 invalid) | 0x03 | R |
| +01 | D24001 (Ch1 U1) | Whole Register | D24001 | Indoor Unit U - Indoor Unit Address (0-254, >254 invalid) | 0x03 | R |
| +02 | D24002 (Ch1 U1) | Whole Register | D24002 | Indoor Unit U - Lock Bit=1 locked, 0 unlocked | 0x03/0x06/0x10 | R/W |
| +03 | D24003 (Ch1 U1) | Whole Register | D24003 | Indoor Unit U - On/Off (0x00 Off, 0x01 On) | 0x03/0x06/0x10 | R/W |
| +04 | D24004 (Ch1 U1) | Whole Register | D24004 | Indoor Unit U - Set Temperature (16-31°C) | 0x03/0x06/0x10 | R/W |
| +05 | D24005 (Ch1 U1) | Whole Register | D24005 | Indoor Unit U - Mode
|
0x03/0x06/0x10 | R/W |
| +06 | D24006 (Ch1 U1) | Whole Register | D24006 | Indoor Unit U - Fan Speed
|
0x03/0x06/0x10 | R/W |
| +07 | D24007 (Ch1 U1) | Whole Register | D24007 | Indoor Unit U - Air Direction (Reserved) | 0x03/0x06/0x10 | R/W |
| +08 | D24008 (Ch1 U1) | Whole Register | D24008 | Indoor Unit U - Temp Lock - Lower Limit (0=unset, 16-31°C) | 0x03/0x06/0x10 | R/W |
| +09 | D24009 (Ch1 U1) | Whole Register | D24009 | Indoor Unit U - Temp Lock - Upper Limit (0=unset, 16-31°C) | 0x03/0x06/0x10 | R/W |
| +10 | D24010 (Ch1 U1) | Whole Register | D24010 | Indoor Unit U - Return Air Temperature | 0x03 | R |
| +11 | D24011 (Ch1 U1) | Whole Register | D24011 | Indoor Unit U - Humidity (Reserved) | 0x03 | R |
| +12 | D24012 (Ch1 U1) | Whole Register | D24012 | Indoor Unit U - Indoor Unit Capacity (self-calculate if unavailable) | 0x03 | R |
| +13 | D24013 (Ch1 U1) | Whole Register | D24013 | Indoor Unit U - Daily Cumulative Run Time (0-1440 min) | 0x03 | R |
| +14 | D24014 (Ch1 U1) | B15-B8 (High) / B7-B0 (Low) | D24014_H / D24014_L | H: Indoor Unit U - Fault Code
Character 1 (ASCII) L: Indoor Unit U - Fault Code Character 2 (ASCII) |
0x03 | R |
| +15 | D24015 (Ch1 U1) | B15-B8 (High) / B7-B0 (Low) | D24015_H / D24015_L | H: Indoor Unit U - Fault Code
Character 3 (ASCII) L: Indoor Unit U - Fault Code Character 4 (ASCII) |
0x03 | R |
- Example: Turn on indoor unit 1 of channel 1 and set the temperature to 25°C
-
Direction Code Request 01 10 5D C3 00 02 04 00 01 00 19 8B 73 Response 01 10 5D C3 00 02 A2 58