System Settings

Offset Register Address Byte/Bit Field ID Function Description Function Code R/W
+000 D65000 B15-B8 (High) D65000_H Set Master Time - Year (increment from 2000, two digits only) 0x10 W
+000 D65000 B7-B0 (Low) D65000_L Set Master Time - Month 0x10 W
+001 D65001 B15-B8 (High) D65001_H Set Master Time - Day 0x10 W
+001 D65001 B7-B0 (Low) D65001_L Set Master Time - Hour 0x10 W
+002 D65002 B15-B8 (High) D65002_H Set Master Time - Minute 0x10 W
+002 D65002 B7-B0 (Low) D65002_L Set Master Time - Second 0x10 W
+003 D65003 Whole Register D65003 Reserved - -
+005 D65005 Whole Register D65005 Device Reboot
  • 0x0080 Master Reboot
  • 0x0001-0x0016 Channel Reboot
  • 0x0040 All Channels Reboot
0x10 W
Note:
  1. Each time the system is powered up, the host computer must send a time synchronisation command. The controller will only commence normal operation once the system has successfully synchronised the time.
  2. It is recommended that the host computer issue a system time synchronisation command every few hours.
Example 1: Set the controller time to October 1, 2024, 10:08:00.
Direction Code
Request 01 10 FD E8 00 03 06 18 0A 01 0A 08 00 E6 74
Response 01 10 FD E8 00 03 31 90
Example 2: Reboot the all channels.
Direction Code
Request 01 10 FD ED 00 01 02 00 40 9C 12
Response 01 10 FD ED 00 01 A0 50