Commands for Calibration Settings
The device supports multiple commands for calibration settings.
Command description:
| Item | Channel | Type | Byte | Description |
|---|---|---|---|---|
| Valve Opening Range | f9 | 4b | 2 | Byte 1: Min. valve opening,
UINT8, Unit: % Byte 2: Max. valve opening, UINT8, Unit: % |
| Thermal Conduction Calibration | f9 | 51 | 1 | 00=Disable, 01=Enable
(Default) Available only when Ambient Temperature Source is set to Internal NTC. |
| Temperature Calibration | ff | ab | 3 | Byte 1: 00=Disable,
01=Enable Byte 2-3: Calibration value, INT16/100, range: -60-60, Unit: °C |
| Motor Stroke Calibration | ff | ad | 1 | ff |
- Example:
-
- Calibrate stroke once.
ffadff Reply:08e500 Channel Type Value 08 e5 00 = Success - Enable temperature calibration and set the calibration value.
ffab01e2ff Channel Type Value ff ab 01=Enable Calibration value: e2 ff=> ff e2 =-30/100=-0.3°C
- Calibrate stroke once.