Commands for General Setting
The device supports multiple commands for general settings.
Command description:
| Item | Channel | Type | Byte | Description | ||||
|---|---|---|---|---|---|---|---|---|
| Ambient Temperature | 03 | - | 3 | Byte 1-2: Temperature,
INT16/100 Byte 3: ff Available only when Ambient Temperature Source is set to LoRa Downlink. |
||||
| Non-heating Period Reporting Interval | f9 | 32 | 2 |
UINT16, Unit: min, Range: 5-1440, Default: 1440 |
||||
| Heating Date | f9 | 33 | 4 | Byte 1: Start month, range:
1-12 Byte 2: Start day, range: 1-31 |
||||
| Ambient Temperature Display | f9 | 36 | 1 | 00 = Disable, 01 = Enable | ||||
| Local Modification Report | f9 | 3a | 1 | 00 = Disable, 01 = Enable Available only when Temperature Control Algorithm is set to Built-in PID. |
||||
| Non-heating Period Valve Status | f9 | 3b | 1 | 00 = Fully closed, 01 = Fully open | ||||
| Valve Descaling | f9 | 3c | 1 | 00 = Disable, 01 = Enable | ||||
| Mounting Orientation | f9 | 3d | 1 | 00 = Horizontal Installation, 01 = Vertical Installation | ||||
| Temperature Unit | f9 | 3e | 1 | 00 = °C, 01 = °F | ||||
| Ambient Temperature Display Time | f9 | 40 | 1 |
UINT8, Unit: s, Range: 1~10, Default: 2 |
||||
| Valve Emergency Position | f9 | 4a | 1 | UINT8, Unit: %, Range: 0~100, Default: 50 | ||||
| System Key | f9 | 4f | 1 | 00 = Disable, 01 = Enable | ||||
| Device Access Password | f9 | 52 | 6 | Hex to ASCII, Range: 0x21~0x7E | ||||
| Device Configuration Reporting Interval | f9 | 53 | 3 | Byte 1: 00=Disable (Default),
01=Enable Byte 2-3: UINT16, Unit: minute, Range: 60~10080, Default: 1440 |
||||
| Reboot | ff | 10 | 1 | ff | ||||
| Child Locks | ff | 25 | 1 |
|
||||
| Query Device Status | ff | 28 | 1 |
|
||||
| Manual Valve Descaling | ff | 29 | 1 | 00 | ||||
| Time Sync | ff | 3b | 1 | 00=Disable, 02=Enable | ||||
| Sync Time from LNS | ff | 4a | 1 | ff | ||||
| Heating Period Reporting Interval | ff | 8e | 3 | Byte 1: 00 Byte 2-3: UINT16, Unit: minute, Range: 5~1440, Default: 10 |
||||
| External Temperature Timeout Time | ff | c4 | 2 | UINT16, Unit: min, Range: 1-1440, Default: 30 | ||||
| Ambient Temperature Source | ff | c5 | 1 | 00 = Internal NTC, 01 = LoRa Downlink | ||||
| Daylight Saving Time | ff | ba | 10 |
Byte 1: 00 = Disable, 01 = Enable Byte 2: DST bias, unit: min, range: 1-120 Week&Day:
|
||||
| Time Zone | ff | bd | 2 | INT16/60 | ||||
| External Temperature Timeout Control Strategy | ff | f8 | 1 |
|
||||
| Device Reset | ff | fe | 1 | ff |
- Example:
-
- Select ambient temperature source as LoRa Downlink.
ffc501 Channel Type Value ff c5 01 = LoRa Downlink - Reboot the device.
ff10ff - Set the non-heating period reporting interval as 1440 minutes.
f932a005 Channel Type Value f9 32 a0 05 =>05 a0 = 1440min - Set DST time: start time is last Sunday 1:00 of March, end time is last
Sunday 1:00 of October, and bias is 1h (60 minutes).
ffba013c03573c000a573c00 Channel Type Value ff ba 01=Enable DST bias: 3c=>60 mins
Start time: 03=>March, 57=>last (5) Sunday(7), 3c 00 =>00 3c=60 minutes =1:00
End time: 0a=>10=October, 57=>last (5) Sunday(7), 3c 00 =>00 3c=60 minutes =1:00
- Select ambient temperature source as LoRa Downlink.