Commands for Temperature Control Settings
The device supports multiple commands for temperature control settings.
| Item | Channel | Type | Byte | Description |
|---|---|---|---|---|
| Target Temperature Regulation Range | f9 | 35 | 4 |
Byte 1-2: Min. target temperature, INT16/100, Unit: °C, Range: 5-35 Byte 3-4: Max. target temperature, INT16/100, Unit: °C, Range: 5-35 |
| Open Window Valve Status | f9 | 37 | 1 | 00 = Remains unchanged, 01 = Close Valve |
| Platform Algorithm Timeout Time | f9 | 41 | 2 | UINT16, Unit: min, Range: 1-1440, Default: 30 |
| Platform Algorithm Timeout Control Strategy | f9 | 42 | 1 |
|
| Target Temperature for Each Scale Level | f9 | 43 | 3 | Byte 1: Scale Level, UINT8,
Range: 0-5 Byte 2-3: UINT16/100, Unit: °C, Range: 5-35 |
| Target Scale Level | f9 | 44 | 1 | UINT8, Range: 0-5, Default: 3 |
| Target Scale Level Display Time | f9 | 45 | 1 | UINT8, Unit: s, Range: 1-10, Default: 2 |
| Target Temperature Resolution | f9 | 46 | 1 | 00=0.5, 01=1 |
| Target Temperature Display Time | f9 | 47 | 1 | UINT8, Unit: s, Range: 1-10, Default: 2 |
| Open Window Stop Temperature Control Time | f9 | 49 | 2 | UINT16, Unit: min, Range: 1-1440, Default: 30 |
| Valve Opening Display | f9 | 4d | 1 | 00=Disable, 01=Enable Available only when Temperature Control Mode is set to Valve Opening Control Mode. |
| Open Window | ff | 57 | 1 | 00 = Close the window, 01 = Open the window |
| Temperature Control Algorithm | ff | ac | 1 | 00 = Built-in PID, 01 = Platform Algorithm |
| Temperature Control Mode | ff | ae | 1 |
|
| Open Window Detection | ff | af | 5 | Byte 1: 00=Disable,
01=Enable Byte 2-3: Cooling rate, INT16/100, Unit: °C/min, Range: 2-10, Default: 3 |
| Freeze Protection | ff | b0 | 3 | Byte 1: 00=Disable,
01=Enable Byte 2-3: Freeze protection temperature, INT16/100, Unit: °C, Range: 1-5 |
| Target Temperature | ff | b1 | 2 | UINT16/100, Unit: °C, Range:
5-35 Available only when Temperature Control Mode is set to Integrated Control Mode. |
| Temperature Control | ff | b3 | 1 | 00=Disable, 01=Enable |
| Valve Opening | ff | b4 | 1 | Valve opening percent, UINT8, Unit: %, Range: 0~100,Default: 0 |
- Example:
-
- Select temperature control mode as Integrated Control Mode.
ffae01 Channel Type Value ff ae 01 = Integrated Control Mode - Enable the open window detection and configure the related
parameters.
ffaf 012c011e00 Channel Type Value ff af 01 = Enable Cooling rate: 2c 01 => 01 2c = 300/100 = 3°C/min
Stop temperature control time: 1e00 => 001e = 30
- Select temperature control mode as Integrated Control Mode.