Commands for Schedule Settings

The device supports multiple commands for schedule settings.

Command description:
Item Byte Command Description
Schedule Event 3+1 6e + Event ID (1B, 0-15) +00 00=Disable, 01=Enable
Schedule Time 3+2 6e + Event ID (1B, 0-15) +01 UINT16, Range: 0-1439, Unit: min
Schedule Repeat Day 3+1 6e + Event ID (1B, 0-15) +02 Per bit 0=Disable, 1=Enable
Bit 7 6 ... 1 0
0 Sat. ... Mon. Sun.
Temperature Control Mode 3+1 6e + Event ID (1B, 0-15) +03 00=Automatic Temperature Control, 01=Valve Opening Control, 02=Integrated Control
Target Temperature 3+2 6e + Event ID (1B, 0-15) +04 UINT16/100, Unit: °C, Range: 5-35
Valve Opening 3+1 6e + Event ID (1B, 0-15) +05 UINT8, Unit: %
Reporting Interval 3+2 6e + Event ID (1B, 0-15) +09 UINT16, Unit: min, Range: 1-1440
Delete Schedule Event 1+1 5e Event ID, range: 0-15, 0xff=Delete all
Example:
Add a schedule event 1.
6e0000016e000158026e0002506e0003026e0004d0076e00090300
Command Value
6e0000 01=Enable
6e0001 Schedule time: 58 02=> 02 58= 600 minutes = 10:00
6e0002 Repeat day: 50=>0101 0000 =Thursday and Saturday enable
6e0003 Temperature control mode: 02=Integrated Control
6e0004 Target temperature: d0 07=>07 d0=2000/100=20°C
6e0009 Reporting Interval: 03 00=>00 03=3 minutes