Commands for Temperature Control Settings
The device supports multiple commands for temperature control settings.
Command description:
| Item | Byte | Command | Description |
|---|---|---|---|
| Temperature Control | 2+1 | 6500 | 00=Disable, 01=Enable |
| Target Temperature Resolution | 2+1 | 6501 | 00=0.5, 01=1 |
| Min. Target Temperature Regulation Range | 2+2 | 6504 |
INT16/100, Unit: °C, Range: 5-35 |
| Max. Target Temperature Regulation Range | 2+2 | 6505 |
INT16/100, Unit: °C, Range: 5-35 |
| Automatic Temperature Control | 3+2 | 650600 | Target temperature: INT16/100, Unit: °C, Range: 5-35 |
| Valve Opening Control | 3+1 | 650601 | Valve opening, UINT8, Unit: % |
| Integrated Control | 3+2 | 650602 | Target temperature: INT16/100, Unit: °C, Range: 5-35 |
| Target Temperature | 1+2 | 5a | INT16/100, Unit: °C, Range:
5-35 Only works under Automatic Temperature Control or Integrated Control mode |
| Valve Opening | 1+1 | 59 | UINT8, Unit:
% Only works under Valve Opening Control or Integrated Control mode |
| Target Temperature/Valve Opening Change Report | 1+1 | 6f | 00=Disable, 01=Enable |
| Open Window Detection | 1+6 | 66 | Byte 1: 00=Disable,
01=Enable Byte 2-3: Cooling rate, INT16/100, Unit: °C/min, Range: 2-10 |
| Open Window Alarm | 1+1 | 5d | 00=Release, 01=Trigger |
| Freeze Protection | 1+3 | 68 | Byte 1: 00=Disable,
01=Enable Byte 2-3: Freeze protection temperature, INT16/100, Unit: °C, Range: 1-5 |
| Force Heating | 1+1 | 69 | 00=Disable, 01=Enable |
- Example:
-
- Select temperature control mode as Automatic Temperature Control and
configure the related parameters.
650600d007 Command Value 650600 Target temperature: d0 07=>07 d0=2000/100=20°C - Adjust target temperature to 20°C.
5ad007 Command Value 5a d0 07=>07 d0=2000/100=20°C
- Select temperature control mode as Automatic Temperature Control and
configure the related parameters.