Installation

Installation location
  • In order to provide the best data transmission, please ensure the device is deployed within the signal range of the LoRaWAN® gateway and keep it away from metal objects and obstacles.
  • The device must be placed in a horizontal position above the detected object so that it has a clear path to the object. The ultrasonic sensor delivers optimal measurement performance when installed perpendicular to the detected object.
  • The device should be installed at least 30cm away from the side-wall without obstructions blocking the ultrasonic signal If the device needs to be installed on the side wall, please ensure the ultrasonic horn is away from the side wall.
  • Do not install the ultrasonic sensor above the influent stream to ensure the measured surface rather than the incoming stream.
  • The device is not suitable for snow level detection. Please contact us to order a customized version if needed.
  • The measurement accuracy of the device may be affected by environmental factors at the installation location, such as solar radiation and water surface fluctuations.
Installation Steps
Step 1:Drill two holes on the container cover according to the location of device mounting holes.

Step 2:Put the device under container cover and align the holes in order to perfectly screw the bolts into the holes from the other side of the cover.


Besides, the device can also be fixed by two M4 mounting screws and wall plugs.