Downlink Command
This device supports downlink commands for configuration and control. The downlink application port is 85 by default.
General Settings
| Item | Channel | Type | Byte | Description |
|---|---|---|---|---|
| Reboot | ff | 10 | 1 | ff |
| Collect Interval | ff | 02 | 2 | UINT16, Unit: s |
| Report Interval | ff | 03 | 2 | UINT16, Unit: s |
| Tilt & Distance Switch | ff | 3e | 1 | 00 = Disable; 01 = Enable |
|
Distance Measurement |
ff | 56 | 1 | 00 = Disable; 01 = Enable |
|
Installation Height for Bin Mode |
ff | 13 | 2 | 00 = Disable; 01 = Enable |
|
Installation Height |
ff | 77 | 2 | UINT16, Unit: mm |
| Device Mode | ff | 71 | 1 |
00 = Standard Mode; 01 = Bin Mode |
- Example:
-
-
Reboot the device.
ff10ff - Set report interval as 20 minutes.
ff03b004 Channel Type Value ff 03 b004=>04b0=1200s=20 minutes - Set the device as standard mode.
ff7100 Channel Type Value ff 71 00 = Standard Mode -
Enable “Tilt & Distance Switch” feature.
ff3e01 Channel Type Description ff 3e 01 = Enable
-
Threshold Alarm Setting
| Channel | Type | Byte | Description |
|---|---|---|---|
| ff | 06 | 9 |
CTRL(1B)+Min(2B)+Max(2B)+00000000(4B) CTRL: Bit2~Bit0:
Bit5~Bit3:
Bit6=0 Bit7:
|
- Example:
- When the distance is below 20cm or above 80cm, the sensor will send
threshold alarm.
ff068c c800 2003 00000000
Channel Type Value ff 06 CTRL: 8c=10 001 100
100=below or above
001=standard mode
10=enable threshold dismiss report
Min: c8 00 => 00 c8 = 200 mm = 20cm
Max: 2003 => 03 20 = 800 mm = 80cm